The Bard MC4002-B is a controller with enhanced alarm board. It does not support SNMP unless the
Bard HVAC 8612-047 CB5000 Communication Board is added.
The CB5000 is an Ethernet Communication Board (Field-Installed) add-on complete with SNMP Traps and IPV6.
The Bard 2100-6141 Installation manual states;
"The notification setup page is used to determine which alarms are remotely communicated to the offsite monitoring systems. The CB5000 supports email notifications as well as IPV4 and IPV6 SNMP Ver. 2 traps.
Remote SMTP server information and a valid email address are required. For the email notifications to work, the corresponding SNMP traps must be enabled, even if SNMP traps are not going to be used.
SNMP traps may be sent to up to four IP addresses to both IPV4 and IPV6 addresses. The addresses are configured remotely by the IT professionals monitoring these traps. The IP addresses are configured in the MIB file using a standard MIB browser. Each of the traps must be enabled and a valid IP address saved in the MIB file."
For a complete lead/Lag Controller that supports SNMP see the
Bard MC4002-BC Controller. It comes complete with Enhanced Alarm & Ethernet Board with SNMP Traps & IPV6.
Replied on July 09, 2020 by Ori from Industrial Stores