The MC4002-B is a 2-stage lead/lag controller that includes an enhanced alarm and rugged metal enclosure that provides excellent protection.  It operates at 18 to 24V and 50/60 Hz.  FCC, ETL, CE, and CSA certified.

The lead/lag controller is suitable for systems that have with or without economizers, 2-stage or dual compressors, and heat pump applications.  The unit also features a dehumidification control with an electronic programmable design.

The MC4002-B is easy to mount and can be factory or field installed.  The  8612-047A communication board, AB3000-A base alarm board accessories, and 8612-023B Remote Temperature Sensor with 35' Cable, AB3000-B Alarm Board, & MC4002 Lead/Lag Controller replacement parts are also available.
 
Cooling stages 4
Frequency 50/60 Hz
Heating stages (configured for A/C with electric heat): 2
Heating stages (configured for Heat Pump): 4
Operating Temperature 0 to 120°F (-18 to 49°C)
Voltage 18 to 32V
Temperature Accuracy +/- 1F from 60 to 85°F (16 to 30°C)
Approvals FCC, ETL, CE, and CSA certified
Lead/Lag Changeover Time 0 to 30 days
Amperage 1A

Q & A: Ask the Questions, share answers

Do you have questions about this product?


Q: 
Does it support SNMP?
Asked on July 08, 2020 by S from Iowa
1 Answers

Have an answer? Click Here

A: 
The Bard MC4002-B is a controller with enhanced alarm board. It does not support SNMP unless the Bard HVAC 8612-047 CB5000 Communication Board is added.  The CB5000 is an Ethernet Communication Board (Field-Installed) add-on complete with SNMP Traps and IPV6.

The Bard 2100-6141 Installation manual states;

"The notification setup page is used to determine which alarms are remotely communicated to the offsite monitoring systems. The CB5000 supports email notifications as well as IPV4 and IPV6 SNMP Ver. 2 traps.

Remote SMTP server information and a valid email address are required. For the email notifications to work, the corresponding SNMP traps must be enabled, even if SNMP traps are not going to be used.

SNMP traps may be sent to up to four IP addresses to both IPV4 and IPV6 addresses. The addresses are configured remotely by the IT professionals monitoring these traps. The IP addresses are configured in the MIB file using a standard MIB browser. Each of the traps must be enabled and a valid IP address saved in the MIB file."


For a complete lead/Lag Controller that supports SNMP see the Bard MC4002-BC Controller.  It comes complete with Enhanced Alarm & Ethernet Board with SNMP Traps & IPV6.
Replied on July 09, 2020 by Ori from Industrial Stores